SENTINEL PRO On-line Double-Conversion UPS

SENTINEL PRO is the latest evolution of the successful Riello Dialog Plus online UPS. This latest development has been designed with the environment in mind and is part of the Riello ECO Line of UPS.

SENTINEL PRO is an on-line double-conversion UPS offering the highest levels of reliability and protection for critical servers, voice and data processing IT systems.
For long runtime applications, Sentinel Pro (ER models) can be fitted with matching battery extension packs which also include additional battery boost chargers.

In terms of communications, each Sentinel Pro has a built-in mimic panel with an LCD to show input and output voltages, and battery charge status. The inverter is a totally new design, fully microprocessor controlled and constructed to achieve the highest levels of operating efficiency and configuration options. SENTINEL PRO UPS also have USB communication ports as standard, with a built-in expansion slot for additional adapters, protocol converters and relate contact cards.

The UPS is highly efficient. SENTINEL PRO is designed to save energy and has a power-off push-button feature to reduce energy consumption to zero, when no load is connected or switched off.
Sentinel Pro models include 700VA, 1000VA, 1500VA, 2200VA and 3000VA.

 

Models SEP 700  PDF
INPUT
Rated power 700 VA
Voltage 220-230-240 Vac
Voltage tolerance 140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOAD
Frequency 50/60 Hz
Frequency tolerance 50 Hz ± 5% / 60 Hz ± 5%
Power factor > 0.99
Current distorsion ≤7%
BY PASS
Voltage tolerance 180 – 264
Frequency tolerance Frequency selected (from ±0.Hz to ±5Hz configurable)
Number phases 1
OUTPUT and INVERTER OUTPUT
Rated power 700 VA
Active power 560 W
Number phases 1
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Frequency Can be selected: 50 Hz or 60 Hz or self-learning
Voltage distortion with distorcing load < 4%
Voltage distortion with linear load < 2%
OVERLOAD TIMES
100% < Load < 110% 2 minutes
125% = Load < 150% 5 seconds
Load > 150% 1 second
BATTERIES
Type VRLA AGM lead, maintenance-free
Recharge time 2-4 h
ENVIRONMENTAL
Altitude max 6000 m
Color Black
Communication USB / DB9 with RS232 and contacts / Slot for communication interface
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Accessories provided Power cable, serial cable, USB cable, safety manual, quick start, software on CD-ROM
Protection rating 3
Surge capability 300 joule
Marks CE, GS/NEMKO
Line-Interactive/Smart Active efficiency 98%
Noise < 40 dBA @ 1 m
Operating temperature 0°C / +40°C
Relative humidity < 95% not condensed
DATA
Weight 10,9 Kg
Dimensions (h w d) 158x422x235 mm

Models SEP 1000 PDF
INPUT
Rated power 1000 VA
Voltage 220-230-240 Vac
Voltage tolerance 140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOAD
Frequency 50/60 Hz
Frequency tolerance 50 Hz ± 5% / 60 Hz ± 5%
Power factor > 0.99
Current distorsion ≤7%
BY PASS
Voltage tolerance 180 – 264
Frequency tolerance Frequency selected (from ±0.Hz to ±5Hz configurable)
Number phases 1
OUTPUT and INVERTER OUTPUT
Rated power 1000 VA
Active power 800 W
Number phases 1
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Frequency Can be selected: 50 Hz or 60 Hz or self-learning
Voltage distortion with distorcing load < 4%
Voltage distortion with linear load < 2%
OVERLOAD TIMES
100% < Load < 110% 2 minutes
125% = Load < 150% 5 seconds
Load > 150% 1 second
BATTERIES
Type VRLA AGM lead, maintenance-free
Recharge time 2-4 h
ENVIRONMENTAL
Altitude max 6000 m
Color Black
Communication USB / DB9 with RS232 and contacts / Slot for communication interface
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Accessories provided Power cable, serial cable, USB cable, safety manual, quick start, software on CD-ROM
Protection rating 3
Surge capability 300 joule
Marks CE, GS/NEMKO
Line-Interactive/Smart Active efficiency 98%
Noise < 40 dBA @ 1 m
Operating temperature 0°C / +40°C
Relative humidity < 95% not condensed
DATA
Weight 13,3 Kg
Dimensions (h w d) 158x422x235 mm

Models SEP 1000 ER PDF
INPUT
Rated power 1000 VA
Voltage 220-230-240 Vac
Voltage tolerance 140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOAD
Frequency 50/60 Hz
Frequency tolerance 50 Hz ± 5% / 60 Hz ± 5%
Power factor > 0.99
Current distorsion ≤7%
BY PASS
Voltage tolerance 180 – 264
Frequency tolerance Frequency selected (from ±0.Hz to ±5Hz configurable)
Number phases 1
OUTPUT and INVERTER OUTPUT
Rated power 1000 VA
Active power 800 W
Number phases 1
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Frequency Can be selected: 50 Hz or 60 Hz or self-learning
Voltage distortion with distorcing load < 4%
Voltage distortion with linear load < 2%
OVERLOAD TIMES
100% < Load < 110% 2 minutes
125% = Load < 150% 5 seconds
Load > 150% 1 second
BATTERIES
Type VRLA AGM lead, maintenance-free
Recharge time N. A.
ENVIRONMENTAL
Altitude max 6000 m
Color Black
Communication USB / DB9 with RS232 and contacts / Slot for communication interface
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Accessories provided Power cable, serial cable, USB cable, safety manual, quick start, software on CD-ROM
Protection rating 3
Surge capability 300 joule
Marks CE, GS/NEMKO
Line-Interactive/Smart Active efficiency 98%
Noise < 40 dBA @ 1 m
Operating temperature 0°C / +40°C
Relative humidity < 95% not condensed
DATA
Weight 7 Kg
Dimensions (h w d) 158x422x235 mm

Models SEP 1500 PDF
INPUT
Rated power 1500 VA
Voltage 220-230-240 Vac
Voltage tolerance 140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOAD
Frequency 50/60 Hz
Frequency tolerance 50 Hz ± 5% / 60 Hz ± 5%
Power factor > 0.99
Current distorsion ≤7%
BY PASS
Voltage tolerance 180 – 264
Frequency tolerance Frequency selected (from ±0.Hz to ±5Hz configurable)
Number phases 1
OUTPUT and INVERTER OUTPUT
Rated power 1500 VA
Active power 1200 W
Number phases 1
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Frequency Can be selected: 50 Hz or 60 Hz or self-learning
Voltage distortion with distorcing load < 4%
Voltage distortion with linear load < 2%
OVERLOAD TIMES
100% < Load < 110% 2 minutes
125% = Load < 150% 5 seconds
Load > 150% 1 second
BATTERIES
Type VRLA AGM lead, maintenance-free
Recharge time 2-4 h
ENVIRONMENTAL
Altitude max 6000 m
Color Black
Communication USB / DB9 with RS232 and contacts / Slot for communication interface
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Accessories provided Power cable, serial cable, USB cable, safety manual, quick start, software on CD-ROM
Protection rating 3
Surge capability 300 joule
Marks CE, GS/NEMKO
Line-Interactive/Smart Active efficiency 98%
Noise < 40 dBA @ 1 m
Operating temperature 0°C / +40°C
Relative humidity < 95% not condensed
DATA
Weight 14,8 Kg
Dimensions (h w d) 158x422x235 mm

Models SEP 2200 PDF
INPUT
Rated power 2200 VA
Voltage 220-230-240 Vac
Voltage tolerance 140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOAD
Frequency 50/60 Hz
Frequency tolerance 50 Hz ± 5% / 60 Hz ± 5%
Power factor > 0.99
Current distorsion ≤7%
BY PASS
Voltage tolerance 180 – 264
Frequency tolerance Frequency selected (from ±0.Hz to ±5Hz configurable)
Number phases 1
OUTPUT and INVERTER OUTPUT
Rated power 2200 VA
Active power 1760 W
Number phases 1
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Frequency Can be selected: 50 Hz or 60 Hz or self-learning
Voltage distortion with distorcing load < 4%
Voltage distortion with linear load < 2%
OVERLOAD TIMES
100% < Load < 110% 2 minutes
125% = Load < 150% 5 seconds
Load > 150% 1 second
BATTERIES
Type VRLA AGM lead, maintenance-free
Recharge time 2-4 h
ENVIRONMENTAL
Altitude max 6000 m
Color Black
Communication USB / DB9 with RS232 and contacts / Slot for communication interface
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Accessories provided Power cable, serial cable, USB cable, safety manual, quick start, software on CD-ROM
Protection rating 3
Surge capability 300 joule
Marks CE, GS/NEMKO
Line-Interactive/Smart Active efficiency 98%
Noise < 40 dBA @ 1 m
Operating temperature 0°C / +40°C
Relative humidity < 95% not condensed
DATA
Weight 25,6 Kg
Dimensions (h w d) 190x446x333 mm

Models SEP 2200 ER  PDF
INPUT
Rated power 2200 VA
Voltage 220-230-240 Vac
Voltage tolerance 140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOAD
Frequency 50/60 Hz
Frequency tolerance 50 Hz ± 5% / 60 Hz ± 5%
Power factor > 0.99
Current distorsion ≤7%
BY PASS
Voltage tolerance 180 – 264
Frequency tolerance Frequency selected (from ±0.Hz to ±5Hz configurable)
Number phases 1
OUTPUT and INVERTER OUTPUT
Rated power 2200 VA
Active power 1760 W
Number phases 1
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Frequency Can be selected: 50 Hz or 60 Hz or self-learning
Voltage distortion with distorcing load < 4%
Voltage distortion with linear load < 2%
OVERLOAD TIMES
100% < Load < 110% 2 minutes
125% = Load < 150% 5 seconds
Load > 150% 1 second
BATTERIES
Type VRLA AGM lead, maintenance-free
Recharge time N. A.
ENVIRONMENTAL
Altitude max 6000 m
Color Black
Communication USB / DB9 with RS232 and contacts / Slot for communication interface
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Accessories provided Power cable, serial cable, USB cable, safety manual, quick start, software on CD-ROM
Protection rating 3
Surge capability 300 joule
Marks CE, GS/NEMKO
Line-Interactive/Smart Active efficiency 98%
Noise < 40 dBA @ 1 m
Operating temperature 0°C / +40°C
Relative humidity < 95% not condensed
DATA
Weight 10,6 Kg
Dimensions (h w d) 190x446x333 mm

Models SEP 3000  PDF
INPUT
Rated power 3000 VA
Voltage 220-230-240 Vac
Voltage tolerance 140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOAD
Frequency 50/60 Hz
Frequency tolerance 50 Hz ± 5% / 60 Hz ± 5%
Power factor > 0.99
Current distorsion ≤7%
BY PASS
Voltage tolerance 180 – 264
Frequency tolerance Frequency selected (from ±0.Hz to ±5Hz configurable)
Number phases 1
OUTPUT and INVERTER OUTPUT
Rated power 3000 VA
Active power 2400 W
Number phases 1
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Frequency Can be selected: 50 Hz or 60 Hz or self-learning
Voltage distortion with distorcing load < 4%
Voltage distortion with linear load < 2%
OVERLOAD TIMES
100% < Load < 110% 2 minutes
125% = Load < 150% 5 seconds
Load > 150% 1 second
BATTERIES
Type VRLA AGM lead, maintenance-free
Recharge time 2-4 h
ENVIRONMENTAL
Altitude max 6000 m
Color Black
Communication USB / DB9 with RS232 and contacts / Slot for communication interface
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Accessories provided Power cable, serial cable, USB cable, safety manual, quick start, software on CD-ROM
Protection rating 3
Surge capability 300 joule
Marks CE, GS/NEMKO
Line-Interactive/Smart Active efficiency 98%
Noise < 40 dBA @ 1 m
Operating temperature 0°C / +40°C
Relative humidity < 95% not condensed
DATA
Weight 28 Kg
Dimensions (h w d) 190x446x333 mm

Models SEP 3000 ER  PDF
INPUT
Rated power 3000 VA
Voltage 220-230-240 Vac
Voltage tolerance 140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOAD
Frequency 50/60 Hz
Frequency tolerance 50 Hz ± 5% / 60 Hz ± 5%
Power factor > 0.99
Current distorsion ≤7%
BY PASS
Voltage tolerance 180 – 264
Frequency tolerance Frequency selected (from ±0.Hz to ±5Hz configurable)
Number phases 1
OUTPUT and INVERTER OUTPUT
Rated power 3000 VA
Active power 2400 W
Number phases 1
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Frequency Can be selected: 50 Hz or 60 Hz or self-learning
Voltage distortion with distorcing load < 4%
Voltage distortion with linear load < 2%
OVERLOAD TIMES
100% < Load < 110% 2 minutes
125% = Load < 150% 5 seconds
Load > 150% 1 second
BATTERIES
Type VRLA AGM lead, maintenance-free
Recharge time N. A.
ENVIRONMENTAL
Altitude max 6000 m
Color Black
Communication USB / DB9 with RS232 and contacts / Slot for communication interface
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Accessories provided Power cable, serial cable, USB cable, safety manual, quick start, software on CD-ROM
Protection rating 3
Surge capability 300 joule
Marks CE, GS/NEMKO
Line-Interactive/Smart Active efficiency 98%
Noise < 40 dBA @ 1 m
Operating temperature 0°C / +40°C
Relative humidity < 95% not condensed
DATA
Weight 14 Kg
Dimensions (h w d) 190x446x333 mm

Kaejean Service Monthly Vision Battery Special Sales