SENTINEL DUAL SDH 1000-3000 VA

SENTINEL DUAL is the high density version of the Premium Pro range of double-conversion on-line UPS.

SENTINEL DUAL is designed to power critical loads such as servers, storage systems, telephone equipment, medical systems and industrial applications.

The UPS is ideal for Blade servers with an input power factor close to Unity (1). The UPS has can be used as tower UPS or within a rackmount cabinet, and takes up only 2U in height.

SENTINEL DUAL has a modern design, choice of functional formats, and represents the state-of-the-art technology from the Riello UPS research & development team. The UPS can achieve an on-line
operating efficiency of 92%.
For critical business continuity applications requiring long runtimes, SENTINEL DUAL can be installed with battery extension packs (ER models) with their own internal battery chargers to maintain sensible recharge times.
The UPS also incorporates the Riello UPS ‘power-off’ function found in other ECO Line UPS. Premium Dual is designed to save energy when no loads are connected.

 

Models SDH 1000  PDF
INPUT
Rated power 1000 VA
Voltage 220-230-240 Vac
Voltage tolerance 140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOAD
Frequency 50/60 Hz
Frequency tolerance 50 Hz ± 5% / 60 Hz ± 5%
Power factor > 0.99
Current distorsion ≤7%
BY PASS
Voltage tolerance 180 – 264
Frequency tolerance Frequency selected (from ±0.Hz to ±5Hz configurable)
Number phases 1
OUTPUT and INVERTER OUTPUT
Rated power 1000 VA
Active power 800 W
Number phases 1
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Frequency Can be selected: 50 Hz or 60 Hz or self-learning
Voltage distortion with distorcing load < 4%
Voltage distortion with linear load < 2%
OVERLOAD TIMES
100% < Load < 110% 2 minutes
125% = Load < 150% 5 seconds
Load > 150% 1 second
BATTERIES
Type VRLA AGM lead, maintenance-free
Recharge time 2-4 h
ENVIRONMENTAL
Altitude max 6000 m
Color Black
Communication USB / DB9 with RS232 and contacts / Slot for communication interface
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Accessories provided Power cable, serial cable, USB cable, safety manual, quick start, software on CD-ROM
Protection rating 3
Surge capability 300 joule
Marks CE, GS/NEMKO
Line-Interactive/Smart Active efficiency 98%
Noise < 40 dBA @ 1 m
Operating temperature 0°C / +40°C
Relative humidity < 95% not condensed
DATA
Weight 13,3 Kg
Dimensions (h w d) 158x422x235 mm

Models SDH 1500  PDF
INPUT
Rated power 1500 VA
Voltage 220-230-240 Vac
Voltage tolerance 140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOAD
Frequency 50/60 Hz
Frequency tolerance 50 Hz ± 5% / 60 Hz ± 5%
Power factor > 0.99
Current distorsion ≤7%
BY PASS
Voltage tolerance 180 – 264
Frequency tolerance Frequency selected (from ±0.Hz to ±5Hz configurable)
Number phases 1
OUTPUT and INVERTER OUTPUT
Rated power 1500 VA
Active power 1350 W
Number phases 1
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Frequency Can be selected: 50 Hz or 60 Hz or self-learning
Voltage distortion with distorcing load < 4%
Voltage distortion with linear load < 2%
OVERLOAD TIMES
100% < Load < 110% 1 minutes
125% = Load < 150% 4 seconds
Load > 150% 0,5 second
BATTERIES
Type VRLA AGM lead, maintenance-free
Recharge time 2-4 h
ENVIRONMENTAL
Altitude max 6000 m
Color Black
Communication USB / DB9 with RS232 and contacts / Slot for communication interface
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Accessories provided Power cable, serial cable, USB cable, safety manual, quick start, software downloadable
Protection rating IP20
Surge capability 300 joule
Marks CE
Line-Interactive/Smart Active efficiency 98%
Noise < 40 dBA @ 1 m
Operating temperature 0°C / +40°C
Relative humidity < 95% not condensed
DATA
Weight 18 Kg
Dimensions (h w d) 450x87x425/87(2U)x450x425 mm

Models SDH 2200  PDF
INPUT
Rated power 1000 VA
Voltage 220-230-240 Vac
Voltage tolerance 140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOAD
Frequency 50/60 Hz
Frequency tolerance 50 Hz ± 5% / 60 Hz ± 5%
Power factor > 0.99
Input current ≤7% A
Current distorsion ≤7%
BY PASS
Voltage tolerance 200 – 253
Frequency tolerance Frequency selected (from ±0.Hz to ±5Hz configurable)
Number phases 1
OUTPUT and INVERTER OUTPUT
Rated power 2200 VA
Active power 1980 W
Number phases 1
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Frequency Can be selected: 50 Hz or 60 Hz or self-learning
Voltage distortion with distorcing load < 4%
Voltage distortion with linear load < 2%
OVERLOAD TIMES
100% < Load < 110% 1 minutes
125% = Load < 150% 4 seconds
Load > 150% 0,5 second
BATTERIES
Type VRLA AGM lead, maintenance-free
Recharge time 2-4 h
ENVIRONMENTAL
Altitude max 6000 m
Color Black
Communication USB / DB9 with RS232 and contacts / Slot for communication interface
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Accessories provided Power cable, serial cable, USB cable, safety manual, quick start, software on CD-ROM
Protection rating 3
Surge capability 300 joule
Marks CE
Line-Interactive/Smart Active efficiency 98%
Noise < 40 dBA @ 1 m
Operating temperature 0°C / +40°C
Relative humidity < 95% not condensed
DATA
Weight 13,3 Kg
Dimensions (h w d) 158x422x235 mm

Models SDH 2200 ER  PDF
INPUT
Rated power 2200 VA
Voltage 220-230-240 Vac
Voltage tolerance 140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOAD
Frequency 50/60 Hz
Frequency tolerance 50 Hz ± 5% / 60 Hz ± 5%
Power factor > 0.99
Current distorsion ≤7%
BY PASS
Voltage tolerance 200 – 253
Frequency tolerance Frequency selected (from ±0.Hz to ±5Hz configurable)
Number phases 1
OUTPUT and INVERTER OUTPUT
Rated power 2200 VA
Active power 1760 W
Number phases 1
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Frequency Can be selected: 50 Hz or 60 Hz or self-learning
Voltage distortion with distorcing load < 4%
Voltage distortion with linear load < 2%
OVERLOAD TIMES
100% < Load < 110% 1 minutes
125% = Load < 150% 4 seconds
Load > 150% 0,5 second
BATTERIES
Type VRLA AGM lead, maintenance-free
Recharge time 2-4 h
ENVIRONMENTAL
Altitude max 6000 m
Color Black
Communication USB / DB9 with RS232 and contacts / Slot for communication interface
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Accessories provided Power cable, serial cable, USB cable, safety manual, quick start, software downloadable
Protection rating IP20
Surge capability 300 joule
Marks CE
Line-Interactive/Smart Active efficiency 98%
Noise < 40 dBA @ 1 m
Operating temperature 0°C / +40°C
Relative humidity < 95% not condensed
DATA
Weight 15 Kg
Dimensions (h w d) 450x87x625/87(2U)x450x625 mm

Models SDH 3000  PDF
INPUT
Rated power 3000 VA
Voltage 220-230-240 Vac
Voltage tolerance 140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOAD
Frequency 50/60 Hz
Frequency tolerance 50 Hz ± 5% / 60 Hz ± 5%
Power factor > 0.99
Current distorsion ≤7%
BY PASS
Voltage tolerance 200 – 253
Frequency tolerance Frequency selected (from ±0.Hz to ±5Hz configurable)
Number phases 1
OUTPUT and INVERTER OUTPUT
Rated power 3000 VA
Active power 2700 W
Number phases 1
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Frequency Can be selected: 50 Hz or 60 Hz or self-learning
Voltage distortion with distorcing load < 4%
Voltage distortion with linear load < 2%
OVERLOAD TIMES
100% < Load < 110% 1 minutes
125% = Load < 150% 4 seconds
Load > 150% 0,5 second
BATTERIES
Type VRLA AGM lead, maintenance-free
Recharge time 2-4 h
ENVIRONMENTAL
Altitude max 6000 m
Color Black
Communication USB / DB9 with RS232 and contacts / Slot for communication interface
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Accessories provided Power cable, serial cable, USB cable, safety manual, quick start, software on CD-ROM
Protection rating IP20
Surge capability 300 joule
Marks CE
Line-Interactive/Smart Active efficiency 98%
Noise < 40 dBA @ 1 m
Operating temperature 0°C / +40°C
Relative humidity < 95% not condensed
DATA
Weight 31 Kg
Dimensions (h w d) 450x87x625/87(2U)x450x625 mm

Models SDH 3000 ER  PDF
INPUT
Rated power 3000 VA
Voltage 220-230-240 Vac
Voltage tolerance 140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOAD
Frequency 50/60 Hz
Frequency tolerance 50 Hz ± 5% / 60 Hz ± 5%
Power factor > 0.99
Current distorsion ≤7%
BY PASS
Voltage tolerance 200 – 253
Frequency tolerance Frequency selected (from ±0.Hz to ±5Hz configurable)
Number phases 1
OUTPUT and INVERTER OUTPUT
Rated power 3000 VA
Active power 2400 W
Number phases 1
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Frequency Can be selected: 50 Hz or 60 Hz or self-learning
Voltage distortion with distorcing load < 4%
Voltage distortion with linear load < 2%
OVERLOAD TIMES
100% < Load < 110% 1 minutes
125% = Load < 150% 4 seconds
Load > 150% 0,5 second
BATTERIES
Type VRLA AGM lead, maintenance-free
Recharge time 2-4 h
ENVIRONMENTAL
Altitude max 6000 m
Color Black
Communication USB / DB9 with RS232 and contacts / Slot for communication interface
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Accessories provided Power cable, serial cable, USB cable, safety manual, quick start, software on CD-ROM
Protection rating IP20
Surge capability 300 joule
Marks CE
Line-Interactive/Smart Active efficiency 98%
Noise < 40 dBA @ 1 m
Operating temperature 0°C / +40°C
Relative humidity < 95% not condensed
DATA
Weight 15 Kg
Dimensions (h w d) 450x87x625/87(2U)x450x625 mm

Kaejean Service Monthly Vision Battery Special Sales