SENTINEL DUAL (high power)

The SENTINEL DUAL (High Power) range is available in 3.3-4-5-6-8-10kVA single-phase models and 6.5-8-10kVA three-phase/single-phase models, with on-line double conversion (VFI) technology.
The DIALOG DUAL range may be placed directly on the floor or mounted in 19” rackmount cabinets such as the Multi Shelter range.

In terms of technology, features (selectable On-line, Economy and Smart Active operating modes), and diagnostics such as the digital display, RS232 and USB interfaces, network adaptor card option and PowerShield³ software include. SENTINEL DUAL (High Power) is easily the best solution for protecting “mission critical” applications requiring the highest levels of reliability.

SENTINEL DUAL (High Power) is ideally suited for a whole range of applications from IT to security.

Models SDL 3300  PDF
INPUT
Rated power 3300 VA
Voltage 220-230-240 Vac
Frequency 50/60 Hz ± 5 Hz
Power factor >0.98
Current distorsion ≤7%
BY PASS
Voltage tolerance 180÷264 Vac (selectable in Economy Mode and SMART ACTIVE Mode)
Frequency tolerance Selected frequency ± 5% (user configurable)
OUTPUT and INVERTER OUTPUT
Rated power 3300 VA
Active power 2300 W
Number phases 1
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Frequency 50/60 Hz selectable
Voltage distortion with distorcing load <5%
Voltage distortion with linear load <3%
OVERLOAD TIMES
100% < Load < 110% 1 min
Load > 150% 0.5 s
BATTERIES
Recharge time 2÷4 h
ENVIRONMENTAL
Color Dark grey
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Accessories provided 2 output supply cables 10 A; 1 plug IEC-16 A; software; serial cable; tools for mimic panel
Protection rating 3
Protections Overload – short-circuit – overvoltage – undervoltage – temperature – low battery
Line-Interactive/Smart Active efficiency 98%
Noise
Operating temperature 0 ÷ 40 °C
Relative humidity <95% no condensing
DATA
Weight 38 Kg
Dimensions (h w d) 455x175x520/175(4U)x483x520 mm

Models SDL 4000  PDF
INPUT
Rated power 4000 VA
Voltage 220-230-240 Vac
Frequency 50/60 Hz ± 5 Hz
Power factor >0.98
Current distorsion ≤7%
BY PASS
Voltage tolerance 180÷264 Vac (selectable in Economy Mode and SMART ACTIVE Mode)
Frequency tolerance Selected frequency ± 5% (user configurable)
OUTPUT and INVERTER OUTPUT
Rated power 4000 VA
Active power 2400 W
Number phases 1
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Frequency 50/60 Hz selectable
Voltage distortion with distorcing load <5%
Voltage distortion with linear load <3%
OVERLOAD TIMES
100% < Load < 110% 1 min
Load > 150% 0.5 s
BATTERIES
Recharge time 2÷4 h
ENVIRONMENTAL
Color Dark grey
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Accessories provided 2 output supply cables 10 A; 1 plug IEC-16 A; software; serial cable; tools for mimic panel
Protection rating 3
Protections Overload – short-circuit – overvoltage – undervoltage – temperature – low battery
Line-Interactive/Smart Active efficiency 98%
Noise
Operating temperature 0 ÷ 40 °C
Relative humidity <95% no condensing
DATA
Weight 40 Kg
Dimensions (h w d) 455x175x520/175(4U)x483x520 mm

Models SDL 5000  PDF
INPUT
Rated power 5000 VA
Voltage 220-230-240 Vac
Frequency 50/60 Hz ± 5 Hz
Power factor >0.98
Current distorsion ≤5%
BY PASS
Voltage tolerance 180÷264 Vac (selectable in Economy Mode and SMART ACTIVE Mode)
Frequency tolerance Selected frequency ± 5% (user configurable)
OUTPUT and INVERTER OUTPUT
Rated power 5000 VA
Active power 4500 W
Number phases 1
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Frequency 50/60 Hz selectable
Voltage distortion with distorcing load <5%
Voltage distortion with linear load <3%
OVERLOAD TIMES
100% < Load < 110% 1 min
Load > 150% 0.5 s
BATTERIES
Recharge time 2÷4 h
ENVIRONMENTAL
Color Dark grey
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Accessories provided 2 output supply cables 10 A; 1 plug IEC-16 A; software; serial cable; tools for mimic panel
Protection rating 3
Protections Overload – short-circuit – overvoltage – undervoltage – temperature – low battery
Line-Interactive/Smart Active efficiency 98%
Noise
Operating temperature 0 ÷ 40 °C
Relative humidity <95% no condensing
DATA
Weight 62 Kg
Dimensions (h w d) 455x175x660/175(4U)x483x660 mm

Models SDL 6000  PDF
INPUT
Rated power 6000 VA
Voltage 220-230-240 Vac
Frequency 50/60 Hz ± 5 Hz
Power factor >0.98
Current distorsion ≤5%
BY PASS
Voltage tolerance 180÷264 Vac (selectable in Economy Mode and SMART ACTIVE Mode)
Frequency tolerance Selected frequency ± 5% (user configurable)
OUTPUT and INVERTER OUTPUT
Rated power 6000 VA
Active power 5400 W
Number phases 1
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Frequency 50/60 Hz selectable
Voltage distortion with distorcing load <5%
Voltage distortion with linear load <3%
OVERLOAD TIMES
100% < Load < 110% 1 min
Load > 150% 0.5 s
BATTERIES
Recharge time 2÷4 h
ENVIRONMENTAL
Color Dark grey
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Accessories provided 2 output supply cables 10 A; 1 plug IEC-16 A; software; serial cable; tools for mimic panel
Protection rating 3
Protections Overload – short-circuit – overvoltage – undervoltage – temperature – low battery
Line-Interactive/Smart Active efficiency 98%
Noise
Operating temperature 0 ÷ 40 °C
Relative humidity <95% no condensing
DATA
Weight 64 Kg
Dimensions (h w d) 455x175x660/175(4U)x483x660 mm

Models SDL 8000  PDF
INPUT
Rated power 8000 VA
Voltage 220-230-240 Vac
Frequency 50/60 Hz ± 5 Hz
Power factor >0.98
Current distorsion ≤5%
BY PASS
Voltage tolerance 180÷264 Vac (selectable in Economy Mode and SMART ACTIVE Mode)
Frequency tolerance Selected frequency ± 5% (user configurable)
OUTPUT and INVERTER OUTPUT
Rated power 8000 VA
Active power 7200 W
Number phases 1
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Frequency 50/60 Hz selectable
Voltage distortion with distorcing load <5%
Voltage distortion with linear load <3%
OVERLOAD TIMES
100% < Load < 110% 1 min
Load > 150% 0.5 s
BATTERIES
Recharge time 2÷4 h
ENVIRONMENTAL
Color Dark grey
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Accessories provided 2 output supply cables 10 A; 1 plug IEC-16 A; software; serial cable; tools for mimic panel
Protection rating 3
Protections Overload – short-circuit – overvoltage – undervoltage – temperature – low battery
Line-Interactive/Smart Active efficiency 98%
Noise
Operating temperature 0 ÷ 40 °C
Relative humidity <95% no condensing
DATA
Weight 94 Kg
Dimensions (h w d) 2x(455x175x660)/2×175(4U)x483x660 mm

Models SDL 10000  PDF
INPUT
Rated power 10000 VA
Voltage 220-230-240 Vac
Frequency 50/60 Hz ± 5 Hz
Power factor >0.98
Current distorsion ≤5%
BY PASS
Voltage tolerance 180÷264 Vac (selectable in Economy Mode and SMART ACTIVE Mode)
Frequency tolerance Selected frequency ± 5% (user configurable)
OUTPUT and INVERTER OUTPUT
Rated power 10000 VA
Active power 9000 W
Number phases 1
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Frequency 50/60 Hz selectable
Voltage distortion with distorcing load <5%
Voltage distortion with linear load <3%
OVERLOAD TIMES
100% < Load < 110% 1 min
Load > 150% 0.5 s
BATTERIES
Recharge time 2÷4 h
ENVIRONMENTAL
Color Dark grey
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Accessories provided 2 output supply cables 10 A; 1 plug IEC-16 A; software; serial cable; tools for mimic panel
Protection rating 3
Protections Overload – short-circuit – overvoltage – undervoltage – temperature – low battery
Line-Interactive/Smart Active efficiency 98%
Noise
Operating temperature 0 ÷ 40 °C
Relative humidity <95% no condensing
DATA
Weight 95 Kg
Dimensions (h w d) 2x(455x175x660)/2×175(4U)x483x660 mm

Models SDL 6500 TM  PDF
INPUT
Rated power 6500 VA
Voltage 380-400-415 Vac
Frequency 50/60 Hz ± 5 Hz
Power factor >0.98
Current distorsion ≤5%
BY PASS
Voltage tolerance 180÷264 Vac (selectable in Economy Mode and SMART ACTIVE Mode)
Frequency tolerance Selected frequency ± 5% (user configurable)
OUTPUT and INVERTER OUTPUT
Rated power 6500 VA
Active power 5850 W
Number phases 1
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Frequency 50/60 Hz selectable
Voltage distortion with distorcing load <5%
Voltage distortion with linear load <3%
OVERLOAD TIMES
100% < Load < 110% 1 min
Load > 150% 0.5 s
BATTERIES
Recharge time 2÷4 h
ENVIRONMENTAL
Color Dark grey
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Accessories provided 2 output supply cables 10 A; 1 plug IEC-16 A; software; serial cable; tools for mimic panel
Protection rating 3
Protections Overload – short-circuit – overvoltage – undervoltage – temperature – low battery
Line-Interactive/Smart Active efficiency 98%
Noise
Operating temperature 0 ÷ 40 °C
Relative humidity <95% no condensing
DATA
Weight 93 Kg
Dimensions (h w d) 2x(455x175x660)/2×175(4U)x483x660 mm

Models SDL 8000 TM  PDF
INPUT
Rated power 8000 VA
Voltage 380-400-415 Vac
Frequency 50/60 Hz ± 5 Hz
Power factor >0.98
Current distorsion ≤5%
BY PASS
Voltage tolerance 180÷264 Vac (selectable in Economy Mode and SMART ACTIVE Mode)
Frequency tolerance Selected frequency ± 5% (user configurable)
OUTPUT and INVERTER OUTPUT
Rated power 8000 VA
Active power 7200 W
Number phases 1
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Frequency 50/60 Hz selectable
Voltage distortion with distorcing load <5%
Voltage distortion with linear load <3%
OVERLOAD TIMES
100% < Load < 110% 1 min
Load > 150% 0.5 s
BATTERIES
Recharge time 2÷4 h
ENVIRONMENTAL
Color Dark grey
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Accessories provided 2 output supply cables 10 A; 1 plug IEC-16 A; software; serial cable; tools for mimic panel
Protection rating 3
Protections Overload – short-circuit – overvoltage – undervoltage – temperature – low battery
Line-Interactive/Smart Active efficiency 98%
Noise
Operating temperature 0 ÷ 40 °C
Relative humidity <95% no condensing
DATA
Weight 94 Kg
Dimensions (h w d) 2x(455x175x660)/2×175(4U)x483x660 mm

Models SDL 10000 TM  PDF
INPUT
Rated power 10000 VA
Voltage 380-400-415 Vac
Frequency 50/60 Hz ± 5 Hz
Power factor >0.98
Current distorsion ≤5%
BY PASS
Voltage tolerance 180÷264 Vac (selectable in Economy Mode and SMART ACTIVE Mode)
Frequency tolerance Selected frequency ± 5% (user configurable)
OUTPUT and INVERTER OUTPUT
Rated power 10000 VA
Active power 9000 W
Number phases 1
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Frequency 50/60 Hz selectable
Voltage distortion with distorcing load <5%
Voltage distortion with linear load <3%
OVERLOAD TIMES
100% < Load < 110% 1 min
Load > 150% 0.5 s
BATTERIES
Recharge time 2÷4 h
ENVIRONMENTAL
Color Dark grey
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Accessories provided 2 output supply cables 10 A; 1 plug IEC-16 A; software; serial cable; tools for mimic panel
Protection rating 3
Protections Overload – short-circuit – overvoltage – undervoltage – temperature – low battery
Line-Interactive/Smart Active efficiency 98%
Noise <45 dBA at 1 m
Operating temperature 0 ÷ 40 °C
Relative humidity <95% no condensing
DATA
Weight 95 Kg
Dimensions (h w d) 2x(455x175x660)/2×175(4U)x483x660 mm

Kaejean Service Monthly Vision Battery Special Sales

Check Products